Platinum resistive temperature transducer. Design1 (type PL-cable)

Usage

This temperature transducer is applied for outdoor temperature measurement in systems of control and automation regulation of different purpose

The temperature transducer should be used with a protective sleeve.

Construction

The temperature transducer consists of a sensing element, which is located in a protection tube ∅6mm, and of a cable with the proper amount of wires and proper section.

The isolation of joining wire tips is removed. Dealing with 4-wire circuit, pairs of wires have different length in accordance with the inner connection.

Technical Features

Measuring temperature range,°С from 0 to plus 160 from minus 50 to plus 180
Mounting part length, mm 45; 60; 80; 100; 120; 160; 200; 250
Wiring diagram (circuit) 2-wire; 4-wire;
Class A or В (СТБ EN 60751), AА
Fastening Mounting to a protection tube
Protective fitting, mm ∅6
For measuring temperature range 0-160°С recalibration interval - 4 years;
minus 50-180°С recalibration interval 4 years.

Installation

The temperature transducer is mounted to a pipeline with the help of protection sleeve and weldolets.

Protective sleeve GZ5/8-xx-G1/4 and weldolets BP3 are used for mounting of the temperature transducer with length 45 and 60 mm.

Protective sleeve GZ2/8 and weldolets BP1(or BP2) are used for mounting of temperature transducer with length 45 and 60 mm.

Connecting

Connecting with an external device is made with the help of the proper section of a flexible cable and the amount of wires corresponding to the temperature transducer circuit.

Design Examples

Design ∅D, mm Lраб, mm Fastening NSH Class Circuit tраб,°С Cable, m
ТСП-Н 1.1.21.00.3.3.0/1.5 6 45 In a sleeve Pt100 А 4-wire 0...+160 1,5
ТСП-Н 1.1.02.00.4.1.1/0.5 6 100 In a sleeve Pt100 В 2-wire -50...+180 0.5
ТСП-Н 1.1.00.00.7.1.0/2 6 60 In a sleeve Pt500 В 2-wire 0...+160 2
ТСП-Н 1.1.01.00.3.2.1/1 6 80 In a sleeve Pt100 А 3-wire -50...+180 1
ТСП-Н 1.1.21.00.3.3.1/1 6 45 In a sleeve Pt100 А 4-wire -50..+180 1
If you want to order not mentioned design you should follow the technical features and ordering diagrams of the concrete type of the resistive temperature transducer TSP-N.